Edge-2-Edge
Enables Edge-to-Edge connection of devices from a slave OpenEMS Edge via Modbus. This requires Controller Api Modbus/TCP Read-Write to be active on the slave system, e.g. via the FEMS App Modbus/TCP Schreibzugriff for a FENECON Energy Storage System.
Example application
-
Setup a 'Slave' OpenEMS Edge instance, that controls one or more energy storage systems
-
Component-ID of the energy storage system or the ESS-Cluster is
ess0 -
Activate
Controller Api Modbus/TCP Read-Writeand addess0to the configuredcomponent_ids
-
At this point you can open OpenEMS UI and check the system profile under settings. Click on the ctrlApiModbusTcp0 component and download the generated Modbus/TCP register table. You should find ess0 listed there. An example Excel file can be found here: https://github.com/OpenEMS/openems/tree/develop/io.openems.edge.controller.api.modbus/doc
|
| This is the setup you will find after purchasing a "FEMS App Modbus/TCP Schreibzugriff" for a FENECON Energy Storage System |
-
Setup a 'Master' OpenEMS Edge instance.
-
Configure
Bridge Modbus/TCP:-
id:modbus0 -
ip: IP-Address of the Slave instance
-
-
Configure
Edge-2-Edge ESS:-
id:ess0 -
remoteAccessMode:AccessMode.READ_WRITE(for default Read-Only access this would beAccessMode.READ_ONLY) -
remoteComponentId:ess0 -
modbus_id:modbus0
-
-
Now you are able to access the remote energy storage system as if it was connected locally, e.g. configure a
Controller Ess Fix Active Poweroness0to set a fixed charge or discharge command.
-