Overview

Provides a Controller that charges or discharges a ManagedSymmetricEss from one SoC extreme to the other in configurable steps. After each step is completed, the Controller pauses the ESS for a configurable standby time before continuing to the next step. This is useful for balancing test, capacity tests, calibration cycles, or controlled cycling of a battery system, where a stepwise SoC profile with rest periods between steps is required rather than a continuous full charge/discharge.

Behavior

The Controller runs through the following states:

  • Undefined — Waits until power, SoC, AllowedChargePower and AllowedDischargePower are all defined and valid before starting.

  • Aligning — Drives the ESS toward the configured Direction (Charge or Discharge) first, so that stepping always starts from the correct SoC extreme (0% for Charge, 100% for Discharge).

  • Running — Applies the configured power in the configured Direction until the SoC crosses a socStep boundary, or until the ESS reports it can no longer charge/discharge further (AllowedChargePower/AllowedDischargePower == 0).

  • Paused — Idles the ESS for standbyTime minutes after each step boundary is reached, then resumes Running.

  • Finished — Reached once the ESS can no longer be charged/discharged further in the configured Direction. Terminal state.

Components

Name: Controller Ess Step Soc

Factory-PID: Controller.Ess.StepSoc

Implemented Natures/Interfaces
  • ControllerEssStepSoc

  • Controller

  • OpenemsComponent

Description: Charges or discharges a Managed Symmetric Ess in fixed SoC steps, pausing for a configurable standby time between each step.

Use Cases:

  • Controlled capacity or calibration cycling of a battery system

  • Stepwise SoC profiling with rest periods, e.g. for BMS balancing windows

Configuration:
  • id (String): Unique ID of this Component (default: ctrlEssStepSoc0)

  • alias (String): Human-readable name of this Component; defaults to Component-ID (default: "")

  • enabled (Boolean): Is this Component enabled? (default: true)

  • ess_id (String): ID of the Ess device

  • direction (Direction): Direction of operation — CHARGE or DISCHARGE. If the system is not already at the corresponding empty/full SoC, the Controller first drives it to that starting point (default: CHARGE)

  • power (Integer): Absolute power in Watt used for charging/discharging, per direction (default: none, required)

  • socStep (Integer): Step size in %. E.g. with 10%, the Controller charges/discharges from 0% to 10%, then pauses (default: 10)

  • standbyTime (Integer): Idle time in minutes after each step (default: 10)