Aircooling Seifert

Integration of Seifert air cooling units (enclosure/cabinet coolers) via Modbus.

Overview

Provides integration with Seifert air cooling units that expose a Modbus register table (Carel-based controller). It reads temperatures, operating mode, output states, door contacts, warnings and faults, and writes the cooling/heating setpoints as well as the high/low temperature alarm setpoints from the configuration. Typical use is the climate control of battery or inverter cabinets.

Supported Devices

Seifert air cooling units
  • Type: Air cooling unit with cooling, heating, internal and ambient blowers

  • Communication: Modbus (RTU/TCP via a Modbus bridge)

  • Temperature values use a scale factor of 10 (e.g. 315 equals 31.5 °C)

  • Temperature unit is forced to Celsius on activation

  • Seifert Systems

Components

Air Cooling Seifert

Name: Air Cooling Seifert

Factory-PID: Aircooling.Seifert

Implemented Natures/Interfaces
  • Seifert

  • EventHandler

  • OpenemsComponent

  • ModbusComponent

Description: Reads the status of a Seifert air cooling unit via Modbus and keeps its setpoints in sync with the configured values. The setpoints are written before each cycle’s process image (TOPIC_CYCLE_BEFORE_PROCESS_IMAGE) unless a different write value was already set. The debug log shows the mode state, ambient temperature and internal (control sensor) temperature.

Use Cases:

  • Cooling and heating of electrical cabinets

  • Monitoring of cooler faults and warnings

  • Door contact supervision

Channels (selection)
  • MODE_STATE: Off, Idle, Cooling, Heating, Testing

  • AMBIENT_TEMPERATURE, CONTROL_SENSOR, INTERNAL_AIR_OUTLET_TEMP

  • OUTPUT_STATUS_HEATER, OUTPUT_STATUS_COMPRESSOR, OUTPUT_STATUS_INTERNAL_BLOWER, OUTPUT_STATUS_AMBIENT_BLOWER

  • DOOR_CONTACT_1_STATUS to DOOR_CONTACT_3_STATUS

  • Faults: sensor faults, blower faults, compressor/ice algorithm, high/low internal temperature, phase failure, Carel/inverter communication failure, delta outlet-inlet temperature

  • Warnings: compressor, ambient blower, internal blower

  • Writable: SET_COOLING_SETPOINT, SET_HEATING_SETPOINT, SET_HIGH_TEMP_ALARM_SETPOINT, SET_LOW_TEMP_ALARM_SETPOINT, SET_ENABLE_INPUT_1_INVERT, SET_ENABLE_TEMP_UNIT

Configuration:
  • id (String): Unique ID of the component (default: airCooling0)

  • alias (String): Human-readable name (default: empty)

  • enabled (Boolean): Is this component enabled? (default: true)

  • modbus_id (String): ID of the Modbus bridge (default: modbus0)

  • modbusUnitId (Integer): Unit-ID of the Modbus device

  • coolingSetpoint (Integer): Cooling setpoint, factor 10, e.g. 315 for 31.5 °C

  • heatingSetpoint (Integer): Heating setpoint, factor 10

  • highTempAlarmSetpoint (Integer): High temperature alarm setpoint, factor 10

  • lowTempAlarmSetpoint (Integer): Low temperature alarm setpoint, factor 10