Aircooling Seifert
Integration of Seifert air cooling units (enclosure/cabinet coolers) via Modbus.
Overview
Provides integration with Seifert air cooling units that expose a Modbus register table (Carel-based controller). It reads temperatures, operating mode, output states, door contacts, warnings and faults, and writes the cooling/heating setpoints as well as the high/low temperature alarm setpoints from the configuration. Typical use is the climate control of battery or inverter cabinets.
Supported Devices
-
Type: Air cooling unit with cooling, heating, internal and ambient blowers
-
Communication: Modbus (RTU/TCP via a Modbus bridge)
-
Temperature values use a scale factor of 10 (e.g.
315equals 31.5 °C) -
Temperature unit is forced to Celsius on activation
Components
Air Cooling Seifert
Name: Air Cooling Seifert
Factory-PID: Aircooling.Seifert
-
Seifert
-
EventHandler
-
OpenemsComponent
-
ModbusComponent
Description: Reads the status of a Seifert air cooling unit via Modbus and keeps its setpoints in sync with the configured values. The setpoints are written before each cycle’s process image (TOPIC_CYCLE_BEFORE_PROCESS_IMAGE) unless a different write value was already set. The debug log shows the mode state, ambient temperature and internal (control sensor) temperature.
Use Cases:
-
Cooling and heating of electrical cabinets
-
Monitoring of cooler faults and warnings
-
Door contact supervision
-
MODE_STATE: Off, Idle, Cooling, Heating, Testing -
AMBIENT_TEMPERATURE,CONTROL_SENSOR,INTERNAL_AIR_OUTLET_TEMP -
OUTPUT_STATUS_HEATER,OUTPUT_STATUS_COMPRESSOR,OUTPUT_STATUS_INTERNAL_BLOWER,OUTPUT_STATUS_AMBIENT_BLOWER -
DOOR_CONTACT_1_STATUStoDOOR_CONTACT_3_STATUS -
Faults: sensor faults, blower faults, compressor/ice algorithm, high/low internal temperature, phase failure, Carel/inverter communication failure, delta outlet-inlet temperature
-
Warnings: compressor, ambient blower, internal blower
-
Writable:
SET_COOLING_SETPOINT,SET_HEATING_SETPOINT,SET_HIGH_TEMP_ALARM_SETPOINT,SET_LOW_TEMP_ALARM_SETPOINT,SET_ENABLE_INPUT_1_INVERT,SET_ENABLE_TEMP_UNIT
-
id(String): Unique ID of the component (default:airCooling0) -
alias(String): Human-readable name (default: empty) -
enabled(Boolean): Is this component enabled? (default:true) -
modbus_id(String): ID of the Modbus bridge (default:modbus0) -
modbusUnitId(Integer): Unit-ID of the Modbus device -
coolingSetpoint(Integer): Cooling setpoint, factor 10, e.g.315for 31.5 °C -
heatingSetpoint(Integer): Heating setpoint, factor 10 -
highTempAlarmSetpoint(Integer): High temperature alarm setpoint, factor 10 -
lowTempAlarmSetpoint(Integer): Low temperature alarm setpoint, factor 10